4 Channel Refrigerant Leak Detection System

| April 29, 2016

Critical Environment QCC-frontThe QCC Quad Channel Controller offers four channel configurations for monitoring toxic, combustible and/or refrigerant gases with versatile control functionality for non-hazardous, non-explosion rated, commercial and light industrial applications. It is designed to accept inputs from up to four remote digital and/or analog transmitters using digital or 4-20 mA analog input.

The QCC is available in two models, the QCC-M with Modbus® RS-485 output or the QCC-B with BACnet® RS-485 output for communicating with a Building Automation System (BAS).

Standard features include, three configurable SPDT dry contact relays with field configurable time delays and trigger levels, an LCD display with LED indicators for channel alarm status, relay status and fault conditions, an extensive menu system with password protection, logic control, a USB port for firmware upgrades and a door mounted, loud audible alarm that is ideal for noisy environments.

Optional value added features include: an analog output module with data logging, a manual shutoff switch (meets B52 code requirements), a top mounted strobe and a water tight, door mounted audible alarm

The QCC can be connected to several remote devices such as a remote strobe/horn combo, a Remote Display Module and the LNK-AO Analog Output Peripheral device.

Key Features

  • Up to 4 channels of gas readings in any combination of analog and/or digital transmitters
  • Standard Modbus® RS-485 digital output signal for LAN and WAN communications
  • Optional BACnet® RS-485 output signal for WAN communications only (for communicating with a BAS)
  • Optional two 4-20 mA outputs with data logging
  • 3 dry contact relays, 5-amps @240 volts each
  • 4 line, 20 character LCD display with LED indicators
  • Standard water / dust tight, corrosion resistant enclosure (drip proof); IP54 rated with water tight, door mounted audible alarm installed
  • USB port for firmware upgrades and data logging
  • Thermal resetting fuses
  • RoHS compliant circuit boards

APPLICATIONS

  • Parking Garages
  • Ice Arenas
  • Commercial Indoor Pools
  • Waste Water Treatment Plants
  • Chiller Rooms
  • …and many more

Critical Environment logo1.877.940.8741